GFK-1504N Chapter 9 Discrete Mixed Modules 9-31
IC200MDD846
Mixed Module, Output Relay 2.0 A per Pt Isolated 8 Points /
Input 120 V AC Grouped 8 Points
Module Specifications
8 Positive AC Inputs, one group.
8 Individually-isolated Form A Relay Outputs.
User input/output to logic
(optical) and frame ground
Group to group
Point to point
250 V AC continuous; 1500 V AC for 1 minute
250 V AC continuous; 1500 V AC for 1 minute
Outputs: 250 V AC continuous; 1500 V AC for 1 minute
One LED per point shows individual point on/off state
OK LED indicates backplane power is present
Backplane current consumption
5V output: 300mA maximum Refer to graph
Compatibility
PME programming software
CPU
CPU
CPU
CPU
DBI
EBI
GBI
PBI
All
0 to 132 V AC (47 to 63Hz), 120 V AC nominal
On state current
5mA minimum
On response time
Off response time
1 cycle maximum
2 cycles maximum
Input impedance 8.6kΩ (reactive) at 60Hz, typical
10.32kΩ (reactive) at 50Hz, typical
Output voltage 0 to 125 V DC, 5/24/125 V DC nominal
0 to 265 V AC (47 to 63Hz), 120/240 V AC nominal
Load current 10mA per point minimum
2.0 Amps for 5 to 265 V AC maximum (resistive)
2.0 Amps for 5 to 30 V DC maximum (resistive)
0.2 Amp for 31 to 125 V DC maximum (resistive)
Not applicable (open contact)
On response time
10ms maximum
No internal fuses or snubbers.
20 cycles per minute (inductive load)
Fixed coil, moving armature