GFK-1504N Chapter 12 Analog Mixed I/O Modules 12-7
IC200ALG430
Analog Mixed Module, 12 Bit Input Current 4 Channels and
Output Current 2 Channels
Scaling
The following graphs illustrate the relationship between the input current
measured at the field terminals and the data values for the module.
Count vs Input Current
0 8192 16384 24576 32767
Count
The following equation can be used to calculate counts values:
Counts = ( Current in mA - 4mA) x (32768 / 16.38mA)
For a change to be seen in the reported count value, input current must be
increased by at least 4µA. If the module receives an increase less than 4µA, the
previous count value is still reported. For example:
Current Count
12.194mA 16392