8| Technical data
Tolerance (± 10%) relative to the mean value of the voltage range.
Othervoltagesandtypesofcurrentonrequest.
-Thespecicationsformax.powerconsumptionapplyfor50Hzoperation.
For60Hzoperation,thespecicationshavetobemultipliedbythefactor
1.2. The max. working current remains unchanged.
- Take account of the max. operating current / max. power consumption for
design of fuses, supply lines and safety devices.
Fuse: Consumption category AC3
1
2
Allspecicationsarebasedontheaverageofthevoltagerange
For solder connections
L = low temperature (-35 / 40 °C), M = normal cooling (-10 / 45 °C),
H = air conditioning (5 / 50°C)
sound pressure level measured in
lowreectionmeasuringarea,measuringdistance1m.
Compressor operation at 50 Hz (1450 rpm), refrigerant R404A.
Valuesstatedareaveragevalues,tolerance±2dB(A).
5
3
4
Type
No. of cylinders
Displace-
ment
50/60Hz
(1450 / 1740 rpm)
Electrical data
Weight
Connections
Oil charge
Sound
pressure
level
Voltage Max.
Operating
current
PW 1 + 2
Max.
power
consump-
tion
Starting
current
(rotorlocked)
PW 1 / PW 1 + 2
Discharge
line
DV
Suction
line
SV
m
3
/h A kW A kg
mm (inch) mm (inch)
Ltr. dB(A)
HGX4/465-4
R134a
4
40,5 / 48,6 16 9,4 56 / 73 148
28 (1
1
/
8
)
35 (1
3
/
8
)
2,7
64 / 63 / 62
HGX4/555-4
R134a
48,2 / 57,8 19 11,2 84 / 109 150 66 / 64 / 62
HGX4/650-4
R134a
56,6 / 67,9 22 13,1 84 / 109 152 42 (1
5
/
8
) 69 / 66 / 63
1
2
3
2
4
380-420VY/YY-3-50HzPW
440-480VY/YY-3-60HzPW
PW = Part Winding
Winding ratio: 66% / 33%
L / M / H