27
80290C_MHW_2400_0908_ENG
IInn PP.. 44
Setting Input 4
This menu lets you configure parameters for the input 4 signals.
Probe type, signal, enable custom
linearization, and main input scale
Input 4 Digital Filter
[0.00 ... 20.00] sec
If set to “0” the average filter is excluded on the sampled
value
Decimal Point Position for Scale
Input 4
Size
0 xxxxx
1 xxxx.x
2 xxx.xx
3 xx.xxx
4 x.xxxx
MIN Scale Limit Input 4
Min...Max value assigned to input selected with
parameter TYP4
MAX Scale Limit Input 4
Offset Correction Input 4
[-999 ... +999] scale points
Probe type Scale limits
0 Input disabled
1 0...10V
-19999/99999
2 0...20mA -19999/99999
3 4...20mA -19999/99999
4 potentiometer -19999/99999
+32 enable custom linearization