*) by adding the following numbers to the value shown in the
table, you can enable a series of supplemental functions:
+16 with automatic switching to GO if IPV-SPI > 0,5%
+32 with automatic switching to GO if IPV-SPI > 1%
+64 with automatic switching to GO if IPV-SPI > 2%
+128 with automatic switching to GO if IPV-SPI > 4%
**) For more information on the Self Tuning, Auto Tuning,
Soft Start functions, see paragraph Notes on Operation.
InF Informations
This menu lets you display the state of the controller
SV
F
PV
InF
Software release
Instrument code
0 no error
1 Lo
2 Hi
3 Err
4 Sbr
5 Ebr
6 Ebr.Lo
7 Er.rtd
8 Er.CAL
Error code IN 1
SV
F
PV
UPd
SV
F
PV
(od
SV
F
PV
Err.1
Error code IN 2
SV
F
PV
Err.2
Error code IN 3
SV
F
PV
Err.3
Error code IN 4
SV
F
PV
Err.4
See: General notes
on operation
(FG PID Configuration
This menu lets you configure the various control parameters.
Enable Self Tuning, Auto Tuning, Soft Start (**)
S.tun Continuous Selftuning Softstart
Autotuning
0 NO NO NO
1 YES NO NO
2 NO YES NO
3 YES YES NO
4 NO NO YES
5 YES NO YES
6 - - -
7 - - -
S.tun One-shot Selftuning Softstart
Autotuning
8* WAIT NO NO
9 GO NO NO
10* WAIT YES NO
11 GO YES NO
12* WAIT NO YES
13 GO NO YES
SV
F
PV
SV
F
PV
S.tv
(fG.Pd
A
Error code Fin A
SV
F
PV
Err.5
Error code Fin b
SV
F
PV
Err.6
Positioning decimal point Fin.A
(read only)
Positioning decimal point Fin.b
(read only)
MIN scale limit Fin.A
(read only)
MIN scale limit Fin.b
(read only)
MAX scale limit Fin.A
(read only)
MAX scale limit Fin.b
(read only)
SV
F
PV
dP5.5
SV
F
PV
dP5.6
SV
F
PV
lo5.5
SV
F
PV
lo5.6
SV
F
PV
xi5.5
SV
F
PV
xi5.6
Baudrate Profibus DP
0 12.00 Mbit/s
1 6.00 Mbit/s
2 3.00 Mbit/s
3 1.50 Mbit/s
4 500.00 Kbit/s
5 187.50 Kbit/s
6 93.75 Kbit/s
7 46.45 Kbit/s
8 19.20 Kbit/s
9 9.60 Kbit/s
SV
F
PV
SV
F
PV
SV
F
PV
fieldbus software version
fieldbus instrument code
(read only)
fieldbus Baudrate (read only)
UPd.F
(od.F
bAv.F