4-71
10- 00
PID target value selection
Range
0
: Potentiometer on Keypad
1
: External AVI Analog Signal Input
2
: External ACI Analog Signal Input
3
: Target Frequency set by Communication method
4
: Set from keypad by parameter 10-02
5
: Set from preset frequency
10-00 selections are only effective when frequency source selection is set to PID by parameters
00 - 05 \ 00 - 06= 6.
When 10-00=5, PID target value is set according to Parameter Group 05 “preset frequency”.
I.e. : When 00-05=6, 10-00=5, 10-03=1, 03-00=2, 03-01=3, 03-02=4, turn on S1~S3
sequentially (0 : OFF, 1 : ON), please check the output frequency on display is consistent with
the 05-01 ~ 05-08.
S1
S2
S3
03-00=2
03-01=3
03-02=4
Preset frequency 0 (05-01)
0
0
0
Preset frequency 1 (05-02)
1
0
0
Preset frequency 2 (05-03)
0
1
0
Preset frequency 3 (05-04)
1
1
0
Preset frequency 4 (05-05)
0
0
1
Preset frequency 5 (05-06)
1
0
1
Preset frequency 6 (05-07)
0
1
1
Preset frequency 7 (05-08)
1
1
1
10- 01
PID feedback value selection
Range
0
: Potentiometer on Keypad
1
: External AVI Analog Signal Input
2
: External ACI Analog Signal Input
3
: Communication setting Frequency
Note: 10-00 and 10-01 can not be set to the same value.
10- 02
PID keypad input
Range
0.0~100.0
%
10- 03
PID operation selection
Range
0
: PID Function disabled
1
: FWD Characteristic. (Deviation is D-controlled)
2
: FWD Characteristic. (Feedback is D-controlled)
3
: REV Characteristic. (Deviation is D-controlled)
4
: REV Characteristic. (Feedback is D-controlled)
5
FWD Characteristic. (Frequency Command +Deviation D Control)
6
FWD Characteristic. (Frequency Command + Feedback D Control)
7
Reverse Characteristic. (Frequency Command + Deviation D Control)
8
Reverse Characteristic. (Frequency Command + Feedback D Control)
10- 03 =1.
Ddeviation (target - detected value) is derivative controlled in unit time set in parameter 10-07.