4-35
PWM dead zone at low frequencies below 10Hz causes torque reduction.
02- 16
SLV Without Load Slip Compensation Gain
Range
0~200%
02- 17
SLV With Load Slip Compensation Gain
Range
0~200%
1. When output current <= 02-00 (Motor current without load)
Slip compensation gain :
= [ SLV slip compensation gain(02-13]* [Normal Duty slip compensation gain (02-16]
2. When output current > 02-00 (Motor current with load)
Slip compensation gain:
= [ SLV slip compensation gain(02-13] * Slip compensation gain 1
(According to the diagram below]
02- 18
SLV With Load Torque Compensation Gain
Range
0~200%
Please refer the contents as parameter 02-13/02-14
02- 19
SLV Slip Compensation Select
Range
0: Slip Compensation Select 1
1: Slip Compensation Select 2
When output current lower or equal to 02-00(no load), the value of slip compensation will be
equal to (02-13)*(02-16)(slip compensation select 1).
When output current higher than 02-00(with load), the value of slip compensation will be equal
to (02-13)*(02-17)(slip compensation select 2).
Note: If inverter worked at lower speed with load, please use slip compensation select 2.
i
Slip compensation
gain ( % )
No-load current
02-00
2*INV rating
i
02-17
100
Slip
compensaiton
gain 1