EasyManua.ls Logo

gefran BDI50-3055-KBX-4-NP-F - Page 97

gefran BDI50-3055-KBX-4-NP-F
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-50
04-11
Analog Output (AO) function selection.
Range
0
:Output frequency
1
:Frequency Setting
2
:Output voltage
3
:DC Bus Voltage
4:Output current
Example: Set 04-11 required according to the following table.
0
10V
Xmax
A
Xmax( 04-11)
Xmax / 2
5 V
04-12
AO Gain
Range
0 ~ 1000
%
04-13
AO Bias
Range
0 ~ 100
%
04-14
AO Bias Selection
Range
0
: Positive
1
: Negative
04-15
AO Slope
Range
0
: Positive
1
: Negative
Select the Analog output type for the multifunction analog output on terminal (TM2)
as required by parameter 04-11. Output format is 0-10V dc.
The output voltage level can be scaled and modified by parameters 04-12 to 04-15 If
necessary.
The modification format will be same as the examples shown previously for Analog Voltage
Input (AVI) parameters 4-02 to 4-05.
Note: the max output voltage is 10V due to the hardware of the circuit.
Use external devices that require a maximum of 10V dc signal.
04-16
Potentiometer / frequency curve gain setting
Range
0 ~ 1000
%
04-17
Potentiometer / frequency curve bias (offset) setting
Range
0 ~ 100
%
04-18
Potentiometer / frequency curve bias (offset) signe selection
Range
0
: Positive
1
: Negative
04-19
Potentiometer / frequency slope of the curve selection
Range
0
: Positive
1
: Negative
Setting of frequency (main / alternative) by potentiometer on integrated keypad.
04-11
A
Xmax
0
Output frequency
upper frequency limit
1
Frequency Setting
upper frequency limit
2
Output voltage
Motor Rated Voltage
3
DC Bus Voltage
220V0~400V
380V
0~800V
4
Output current
2 times rated current
of inverter

Table of Contents