Troubleshooting/Quick Reference Guide
Owner’s Manual for Australian 3-Phase 50 Hz Air-Cooled Generator Sets 33
Quick Reference Guide
To clear an active alarm, press OFF button on control panel, then ENTER button, and finally AUTO button. If alarm
reoccurs, contact an IASD.
Active Alarm LED Problem Action Solution
NONE
FLASHING
GREEN
Unit running in AUTO but
no power in house.
Check generator set
MLCB (generator set
disconnect).
Check generator set MLCB (generator set
disconnect). If it is ON, contact an IASD.
HIGH
TEMPERATURE
RED
Unit shuts down during
operation.
Check LEDs / screen
for alarms.
Inspect ventilation around generator set,
intake, exhaust, and rear of unit. If no
obstructions are present, contact an IASD.
OVERLOAD
REMOVE LOAD
RED
Unit shuts down during
operation.
Check LEDs / screen
for alarms.
Clear alarm and remove household loads
from generator set. Put in AUTO and restart.
RPM SENSE
LOSS
RED
Unit was running and
shut down, attempts
to restart.
Incorrect pressure in
fuel field kit.
Check LEDs / screen
for alarms.
Clear alarm and remove household loads
from generator set. Put into AUTO and
restart.
Check fuel field kit pressures switches. If
generator set does not start, contact an
IASD.
NOT ACTIVATED NONE
Unit will not start in
AUTO with utility loss.
Check if screen says
unit not activated.
See Activation in installation manual.
NONE GREEN
Unit will not start in
AUTO with utility loss.
Check screen for start
delay countdown.
If startup delay is greater than expected,
contact an IASD to adjust from 2 to 1500
seconds.
LOW OIL
PRESSURE
RED
Unit will not start in
AUTO with utility loss.
Check LEDs / screen
for alarms.
Check oil level and add oil as needed. If oil
level is correct, contact an IASD.
RPM SENSE
LOSS
RED
Unit will not start in
AUTO with utility loss.
Check LEDs / screen
for alarms.
Clear alarm. Using control panel, check
battery by navigating to BATTERY MENU
option from the MAIN MENU. If battery
condition displays GOOD, contact an IASD.
If control panel displays CHECK BATTERY,
replace battery.
OVERCRANK RED
Unit will not start in
AUTO with utility loss.
Check LEDs / screen
for alarms.
Verify fuel line shutoff valve is ON. Clear
alarm. Start unit in MANUAL. If it does not
start, or starts and runs rough, contact an
IASD.
LOW VOLTS
REMOVE LOAD
RED
Unit will not start in
AUTO with utility loss.
Check LEDs / screen
for alarms.
Clear alarm and remove household loads
from generator set. Put in AUTO and restart.
OVERSPEED RED
Unit will not start in
AUTO with utility loss.
Check LEDs / screen
for alarms.
Contact an IASD.
UNDERVOLTAGE RED
Unit will not start in
AUTO with utility loss.
Incorrect pressure in
fuel field kit.
Check LEDs / screen
for alarms.
Contact an IASD.
Check fuel field kit pressures switches.
UNDERSPEED RED
Unit will not start in
AUTO with utility loss.
Check LEDs / screen
for alarms.
Contact an IASD.
STEPPER
OVERCURRENT
RED
Unit will not start in
AUTO with utility loss.
Check LEDs / screen
for alarms.
Contact an IASD.
WIRING ERROR RED
Unit will not start in
AUTO with utility loss.
Check LEDs / screen
for alarms.
Contact an IASD.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Generac Power Systems G0072190 and is the answer not in the manual?

Generac Power Systems G0072190 Specifications

General IconGeneral
BrandGenerac Power Systems
ModelG0072190
CategoryPortable Generator
LanguageEnglish

Related product manuals