Version: 2020-09-04
36
Copyright of the European Union is effective (Copyright EU) (c) 2019 GENEREX Systems GmbH, Hamburg, Germany, All rights reserved
TEL +49(40)22692910 - EMAIL generex@generex.de - WEB www.generex.de (This and all other product datasheets are available for download.)
Guest access
User guest
Default Password: guest
The guest access is designed to view system monitors without triggering additional functions. Due to this fact, a special feature comes
with this user: If necessary, password queries can be deactivated by administrators.
➔ Enable/disable password query
➔ Enter a new password
➔ Verify password
To use guest access without password query, set the mark for Anonymous Access. Otherwise the CS141 will ask for a valid password.
Note:
The user admin is allowed to manage COM interfaces, but not the user engineer. This is necessary due to the fact, attached monitoring
systems may need to be prepared for a change inside the hardware landscape before local hardware or components will be disabled for
local maintenance duties.
If a technician already "starts" before administrators stop according monitoring services, wrong alarm states may cause trouble.
How to use guest /anonymous login
The guest access can be used for
Normally, the CS141 only provides information via its web interface if a user successfully logs in - a deep link to view the UPS monitor
directly is treated accordingly:
After activating Anonymous authentication, it is possible to view the monitoring screens directly – it is even possible to create a small
html page and set up an i-frame to show it inside larger websites or content management systems. This html code may help you to
create the html webside:
<html><head></head>
<body>
<center>
<p>I-Frame zu der USV mit der IP xxx </p>
<br><hr><br>
<iframe src="http://<Ihre IP>/www/devices/ups/page" height="600" width="850" name="iFrame" title="IFrame zu meiner
USV"></iframe>
</center>
</body></html>
As a result, the UPS monitoring screen will appear inside your html document: