Copyright of the European Union is effective (Copyright EU) (c) 2019 GENEREX Systems GmbH, Hamburg, Germany, All rights reserved
TEL +49(40)22692910 - EMAIL generex@generex.de - WEB www.generex.de (This and all other product datasheets are available for download.)
IP address
Under IP Address, enter the IP address of the authorized computer to allow access to the CS141 device via SNMP v2. Thereby the
name of the community defines the authorization group.
Permission
Defines permissions during access:
Read only Devices dealing inside this permission group have read-only permissions
Read/Write Devices dealing inside this authorization group can read and write /delete data packets.
Set up trap receivers
Set up trap receivers
What are SNMP traps for?
In principle, an agent monitoring a system can unsolicited send a so-called trap packet to its management station should this be
required. Among other things, the status of the monitored device is communicated. On the other hand, the agent can receive and
service requests from his manager. There are two ports required by default:
Port 161 Required by the agent on the device to receive the requests
Port 162 Required by the management station to receive messages
If these ports are blocked, the communication will not work.
Configuring trap receivers on the CS141
The advantage of the trap messages is that the CS141 can automatically inform about changes in the UPS.
To add a new trap receiver, click +,
Since trap messages are sent exclusively to inform about status
changes, no read / write operations permissions are required.
Enter the recipient's IP address as well as a valid community.
With Save button, CS141 takes over the settings and the SNMP agent
will be restarted. The CS141 will not need to be rebooted.