The voltage provided by pin 1, pin 5 and pin 6 is defined by the power supply unit used on the SENSOR MANAGER. The SENSOR
MANAGER itself operates at an operating voltage of 9-24V. If a 12 V power supply is connected, 12 VDC will be offered on these pins
accordingly. When connecting external devices, pay attention to the maximum permissible voltage that may be applied:
Overvoltage can damage or even destroy connected devices. In case of undervoltage, however, connected devices may deliver wrong
results.
On delivery the SENSOR MANAGER comes with a standard power supply providing 12 VDC.
Analog inputs:
Each of the 4 SENSORMANAGER_II physical RJ-12 connectors provide 2 analog inputs on pin 2 and pin 3.
Administrators wishing to connect a third-party device, must set the signal (0-10VDC o. 0 / 4-20mA) of the third-party device to PIN 2 or
pin 3 and pin 4 (ground / GRD).
Digital inputs:
Each of the 4 physical RJ-12 connections of the SENSORMANAGER_II provides a digital input on pin 6.
For Administrators who wish to connect a third-party device:
The high signal (12VDC) from pin 1 must be routed to pin 6 via the signaling contact of the third-party device.
Digital outputs:
Each of the SENSORMANAGER's 4 physical RJ-12 ports provides a digital output on pin 5.
Administrators who wish to connect a third-party device:
The device must be connected to pin 5 (open collector output: + 12VDC / max.30mA) and pin 4 (Ground / GND) are connected.
Note:
How to use third-party sensors
Due to the fact third-party devices do not have the standardized RJ12 port,
our Connection Terminal SM_CON is an easy-to use possibility to connect these
devices to the CS141. By using the SM_CON it is possible to adapt
open line ends to the Rj12 connector directly - No custom plug
Connecting sensors / actuators to the SENSORMANAGER_II
The sensors / actuators for the SENSORMANAGER II can be connected directly to the SENSORMANAGER II RJ12 sockets- ensure to
use the original RJ12 cables supplied with the according sensor.
The SENSORMANANAGER II provides to connect several sensors / actuators to one physical port. The system design provides
following wiring options:
1. A maximum of two analog sensors per port
2. A maximum of one more digital sensor per port
3. A maximum of one digital actuator per port
The sensor manager supports a total installation of 8 analog and 4 digital sensors as well as up to 4 digital actuators.
Sensor connection scenarios: SENSORMANAGER_II.
The SENSORMANAGER II provides various options to connect sensors.
Pin number:
Funktion:
1
9-24VDC, output according to input of supply voltage,
default delivery: 12VDC power supply
2
Analog input channel x (0-10VDC o. 0/4-20mA)
3
Analog input channel x (0-10VDC o. 0/4-20mA)
4
Ground (GND)
5
Digital output (Open-Collector 9-24VDC/max. 30mA,
Default on delivery: 12VDC )
6
Digitalinput (min./max. 9-24V via Pin 1)