The Daisy Chain: Connection
The daisy chain is a sequential arrangement of sensors and actuators. The signal is transmitted from the sensor manager through the
first sensor to the second sensor. In this installation example, a digital third sensor is attached to the second sensor. Please note that no
further digital sensor can be attached to the sensor 3.
The Splitting Plug SPSMRJ connection
If sensors needs be installed in different areas, the signal distribution can be splitted into two wirings. The optional splitting plug will splitt
the signal accordingly. Please note that the sensor manager can only serve two analog sensors per port.
Combined connections: Daisy Chain and Splitting Plug SPSMRJ
This installation constellation extends the existing installation by an actuator and a digital sensor: The port on the sensor manager is
maxed out utilizing a total of 4 devices:
Please note the system design:
This installation design provides the maximum of two analog sensors and one digital sensor as well as one digital output per sensor
manager port.