EasyManua.ls Logo

Genesis SHERLOCK 102 - Setpoint Menu Configuration; Entering the Setpoint Menu; Configuring Oxygen Sensor Setpoints and Delays; Configuring Refrigerant Sensor Setpoints and Delays

Genesis SHERLOCK 102
53 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44-00-0297 SHERLOCK102/202 REV. 4.1 05-02-1532
These Sub-menus are to be followed if the setpoints and alarm
delays for one or all of the control system are to be changed
Prior to changing the control setpoints, ensure that the control
system is in the "IN CHANGE MODE" or "ALL ACCESS
MODE". At DEFAULT SCREEN, press UP/DOWN arrow
button to scroll to the "<SETPOINT MENU>". Press the
SELECT button to enter this menu. Screen entries will only
be shown if their respective control options are installed in the
SYSTEM CONFIG MENU.
To make any changes: Press SELECT button. The dis-
played value should begin to blink. Press UP/DOWN
arrow buttons to change the value. Press SELECT button
to accept the value. Press DOWN button to next entry
This Entry will be shown if sensor A is configured as Oxygen
Sensor in SYSTEM CONFIG MENU.
OXYGEN SENSOR SETPOINT (15.0-25.0)
OXYGEN SENSOR ALARM DELAY (1-10 MINUTES)
This entry will be shown if sensor A is selected as a refrigerant
sensor in the configuration menu
SENSOR A LEVEL 1 ALARM SETPOINT (20-999)
SENSOR A LEVEL 1 ALARM DELAY (1-120 MINUTES)
SENSOR A LEVEL 2 ALARM SETPOINT (20-999)
SENSOR A LEVEL 2 ALARM DELAY (1-120 MINUTES)
Continued on next page
SELECT/
CHANGE
<SETPOINT MENU>
SELECT/
CHANGE
SELECT/
CHANGE
SELECT/
CHANGE
SELECT/
CHANGE
<SET> OXYGEN SNR
ALARM 1, % 15.0
<SET> OXYGEN LOW
ALM DLY,MIN: 1
SETPOINT MENU
SELECT/
CHANGE
SELECT/
CHANGE
<ST>SNR A LEVEL1
ALARM,PPM: 150
SELECT/
CHANGE
SELECT/
CHANGE
<ST>SNR A L1 ALM
DELAY,MIN: 1
SELECT/
CHANGE
SELECT/
CHANGE
<ST>SNR A LEVEL2
ALARM,PPM: 250
SELECT/
CHANGE
SELECT/
CHANGE
<ST>SNR A L2 ALM
DELAY,MIN: 1
REPEAT FOR SENSOR B IF APPLICABLE

Related product manuals