Step 7: Re-Install panel cover, Verify proper operation of interlock. Main breaker ON, generator breaker OFF and generator breaker
CAN NOT be turned on. Generator breaker ON, main breaker OFF and main breaker CAN NOT be turned on.
Generator On Main On
Place Generator start-up procedure label on panel box, Place CAUTION label on panel box and electric meter pan.
The MAIN and the GENERATOR breakers should NEVER be able to be turned on at the same time. If panel cover is removed the
Generator breaker is NEVER to be turned on. If for any reason the interlock does not function properly, DO NOT USE and contact us
immediately at sales@GenInterlock.com for support and instructions.
Thank You for your support,
GenInterlock Team
DISCLAIMER: GenInterlock.com is NOT responsible for misuse or
improper installation. All electrical equipment should be installed and
maintained by qualified personnel. Any consequences arising from
improper use is the responsibility of the user.