Do you have a question about the GenInterlock SIE-L2 and is the answer not in the manual?
Only qualified personnel should work on the panel box.
An amateur should NEVER open the panel box.
Follow all rules and regulations of the National Electric Code.
Place bottom plate from main breaker edge to generator breaker edge.
Turn off main breaker and remove the panel cover.
Drill marked holes on panel cover and remove all burs.
Install bottom and top plates, secure with nuts and thread lock.
Install 2-pole generator breaker and place warning sticker.
Use zip ties to secure breaker around metal plate and top.
Re-install panel cover, verify interlock operation.
Place generator start-up and caution labels on panel box.
GenInterlock.com is not responsible for misuse or improper installation.
Contact sales@GenInterlock.com for support if interlock fails.
| Rated Current | 16A, 20A, 25A, 32A, 40A, 50A, 63A |
|---|---|
| Rated Voltage | 230/400V AC |
| Breaking Capacity | 6 kA |
| Trip Characteristics | C Curve |
| Mechanical Life | 20, 000 operations |
| Electrical Life | 10, 000 operations |
| Operating Temperature | -25°C to +55°C |
| Storage Temperature | -40°C to +70°C |
| Terminal Type | Screw Terminals |
| Standards | IEC/EN 60898-1, IEC 60947-2 |
| Mounting | DIN Rail |