HomeServer 3 - Commissioning
30
10.2006/V 1.0
4.3 Programming via an RS232 connection
You can transfer the changed data directly from the commissioning PC to the HomeSer-
ver as follows:
1. Disconnect the HomeServer from the EIB (if required).
2. Connect the serial (RS232) interface of the HomeServer with a COM interface of your
commissioning PC. Use the supplied commissioning cable to do this.
3. Start the HomeServer Expert on your commissioning PC. Load the sample project
with the changed IP address (if required).
4. Select Transmit. A window, Transm it Pro j ect now appears.
5. Select By serial interface.
6. Enter the number of your serial interface next to Serial interface (e. g. 1).
7. Activate in the Transmission mode area Transmit Data.
8. Switch off the HomeServer. Click on Start. Switch the HomeServer back on. The
data are transferred directly to the HomeServer once you have heard three double-
beeps.
9. Disconnect the direct connection between the HomeServer and the commissioning
PC after the data have been transmitted.
10.Connect the HomeServer to the EIB.