MAR 2018 GFV-305 (Formerly H-3) Page 1 of 11
GENERAL DESCRIPTION
The Globe Model RCW* dry valve is a hydraulically oper-
ated external resetting differential latching style valve. The
Model RCW dry valve is used as an automatic water control
valve in dry applications. The Model RCW dry valve serves
as the primary water control valve installed in the water
supply to a dry sprinkler system incorporating automatic
(closed) sprinklers with compressed air or nitrogen within
the system piping.
Setting of the Model RCW dry valve requires water pressure
in the pressure chamber being maintained on the plunger
rod. The pressure on the plunger rod forces the lever arm/
roller assembly against the clapper which in turn keeps
the supply water from entering the sprinkler system pip-
ing. Water pressure is provided to the pressure chamber
through a connection to the main water supply at a point
upstream of the system main control valve. This connection
also supplies water pressure up to the dry pilot actuator.
The dry pilot actuator is held closed when in the normal set
condition by air pressure in the system piping. When system
air pressure is relieved via one or more operated sprinklers,
the dry pilot actuator will open, allowing the pressurized
water to be evacuated from the pressure chamber.
In the standby condition, the valve is normally closed and
will automatically activate (trip) upon the activation of an au-
tomatic sprinkler, as a result of a re condition. The RCW
valve may also be operated by means of a manual release,
which is provided in the trim, to override the normal activa-
tion sequence described above.
When heat from a re opens an automatic sprinkler, water
pressure in the pressure chamber decays resulting in the
movement of the push rod assembly, releasing the lever
arm/roller assembly from the clapper. The system water
supply pressure forces the valve clapper open resulting in
water ow into the system piping. Upon system activation,
re alarm signaling is provided by means of owing water
through the alarm port/intermediate chamber and associ-
ated alarm line trim. The ow of water activates a pressure
switch which in turn noties local alarms and/or an alarm
signaling monitoring service. After the main control valve
has been shut, the system drained, and any operated
sprinklers replaced, the RCW dry valve is easily set/reset by
means of pushing the reset knob. The system is now ready
for the introduction of compressed air back into the system
piping.
If the speed of operation of the dry valve needs to be in-
creased, an optional accelerator can be utilized to decrease
the trip time of the valve from the operation of a sprinkler or
the inspectors test connection.
TECHNICAL DATA
Approvals
cULus
FM
Maximum System Working Pressure
300 psi (20.6 Bar)
End Connections
Groove x Groove
Materials of Construction
See Technical Datasheet H-1 for materials of
construction for the Model RCW Valve
*Patents Pending
MODEL RCW DRY SYSTEM VALVE
GFV-305 (Formerly H-3)
GFV-305 (Formerly H-3)
4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com
Technical Support 989-414-2600 techservice@globesprinkler.com
MODEL RCW DRY SYS-
TEM
MODEL RCW DRY SYS-
TEM
MODEL RCW DRY SYSTEM VALVE
Question and Answer IconNeed help?

Do you have a question about the Globe RCW and is the answer not in the manual?

Globe RCW Specifications

General IconGeneral
BrandGlobe
ModelRCW
CategoryControl Unit
LanguageEnglish

Summary

Model RCW Dry System Valve

General Description

Provides a detailed explanation of the Model RCW dry valve's operation and application in dry sprinkler systems.

Technical Data

Lists key technical specifications, approvals, maximum working pressure, and end connections for the Model RCW valve.

Dry System Trim Configuration

GDPA vs GDPA-LP Actuator Comparison

Compares the GDPA and GDPA-LP dry pilot actuators, discussing factors influencing fluid delivery time and system pressure.

GDPA-LP Actuator Details

Explains the GDPA-LP actuator, its pressure limitations, identification color, and suitability for specific system types.

Dry Schematic (No Accelerator)

Dry Schematic with Accelerator

Presents the dry system schematic including an accelerator, outlining its integration and effect on system operation.

4-Inch RCW Dry Trim Arrangement

6-Inch RCW Dry Trim Arrangement

4-Inch Accelerator Trim Arrangement

6-Inch Accelerator Trim Arrangement

Details the 6-inch optional accelerator trim arrangement, including components and integration methods.

Accelerator Trim Options

Explains the three different options for accelerator trim and their compatibility with the dry valve.

Installation and Maintenance

Installation Procedure

Provides detailed steps for the correct installation of the RCW Valve, emphasizing orientation and accessibility.

Dry Valve Setting Procedure

Outlines the step-by-step procedure for setting the Model RCW dry system valve after a test or operation.

Model C Accelerator Setting Procedure

Details the procedure for setting the Model C accelerator, including steps for pressure observation and troubleshooting.

Testing Procedures

References NFPA 25 and outlines precautions and steps for testing the system, ensuring safety and proper discharge.

Dry System Trip Test Procedure

Dry System Waterflow Alarm Test

Maintenance Requirements

Ordering Information

Pre-Trimmed Valve Configurations

Details ordering options for pre-trimmed RCW valves, including variations with specific control valves and accelerators.

Non-Assembled and Component Ordering

Lists components and trim kits that must be ordered separately for non-assembled or custom RCW valve configurations.

Globe Product Warranty