PRODUCT-RELATED SAFETY ADVICE
Must be installed by a specialised company in accordance with local
industrial health and safety regulations!
Installation outside the defined EX protection zone!
Escaping, liquid fuels:
• are hazardous for water
• are inflammable
• can ignite and cause burning
• can cause injury through people falling or slipping
Capture fuels during maintenance work!
May not be used in potentially explosive areas!
Can cause an explosion or serious injuries.
Overfill prevention divice type BC-1
INTENDED USE
Operating media
• Diesel fuel • Fuel oil • Water or oil-water mixtures
• Petrol • Heavy heating oil • Liquid fertiliser (AHL, ASL, HAS)
• FAME • Industrial oil • JGS (liquid manure, semi-liquid manure
and silage effluent)
• Urea solution • Vegetable oil
You will find a list of operating media with descriptions, the relevant
standards and the country in which they are used in the Internet at
www.gok-online.de/de/downloads/technische-dokumentation.
Place of operation
May not be used in potentially explosive areas!
Can cause an explosion or serious injuries.
Indicator:
• type BC-1-1, type BC-1-3, type BC-1-4, with protection type IP30, in dry and protected
rooms
•
type BC-1-2, with protection type IP65, indoors and outdoors, if protected against the
weather
Use in areas prone to flooding and risk areas
Damage to the product from flooding
Suitable for installation in areas at risk of flooding only to 10 m water height!
Replace the product after flooding!
INFORMATION FOR THE PLANT OPERATOR
Please ask your specialised company to confirm the proper installation of the
overfill prevention divice on the installation certificate of the specialised company
(see the last two pages).
Probe:
• if the probe is used outdoors, it must be protected with suitable means against penetrating
humidity (e.g. with shrinking tube attached)
pull the protection over the cable and approx. 1cm over the probe and shrink it. The
marking line and the value for Z must be visible
part no. 308 393 _15 700 71 a