Why is my Goodman Amana ComfortNet GMVC8 Furnace blower running constantly with E3 error?
- RRebecca OrtegaAug 17, 2025
If your Goodman furnace's circulator blower runs continuously, but there's no furnace operation, and the integrated control module LED display shows an E3 error code, it could be due to an open primary or auxiliary limit circuit, or an open rollout limit circuit. Check the filters and ductwork for any blockages, and clean the filters or remove any obstructions. It could also be due to insufficient conditioned air over the heat exchanger, so check the circulator blower speed and performance, correcting the speed or replacing the blower motor if needed. Misaligned burners, a blocked flue and/or air inlet pipe, or a failed induced draft blower can also cause this issue; check the burners for proper alignment.