RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
Prior to installation, thoroughly familiarize yourself with this Installation Manual.
Observe all safety warnings. During installation or repair, caution is to be observed.
It is your responsibility to install the product safely and to educate the customer on its safe use.
ARUF**14**/ARPT**14**
1 Important Safety Instructions
The following symbols and labels are used throughout this
manual to indicate immediate or potential safety hazards. It
is the owner’s and installer’s responsibility to read and com-
ply with all safety information and instructions accompanying
these symbols. Failure to heed safety information increases
the risk of personal injury, property damage, and/or product
damage.
ASPT**14**/ASUF**14**
AIR HANDLERS INSTALLATION & OPERATING INSTRUCTIONS
Contents
1 Important Safety Instructions .................................. 1
2 Shipping Inspection ................................................. 2
2.1 Parts ........................................................................3
2.2 Handling ..................................................................3
3 Codes & Regulations................................................ 3
4 Replacement Parts ................................................... 3
5 Pre-Installation Considerations .............................. 3
5.1 Preparation ..............................................................3
5.2 System Matches ......................................................3
5.3 Interconnecting Tubing ............................................3
5.4 Clearances ..............................................................3
5.5 Horizontal Applications ............................................4
6 Installation Location ................................................ 4
6.1 Upflow Installation....................................................4
6.2 Horizontal Left Installation .......................................4
6.3 Downflow/Horizontal Right Installation ....................5
7 Refrigerant Lines ...................................................... 7
7.1 Tubing Size ..............................................................7
7.2 Tubing Preparation ..................................................7
7.3 Special Instructions .................................................8
7.4 Tubing Connections for Flowrator Model .................8
7.5 Tubing Connections for TXV Models .......................8
8 Condensate Drain Lines........................................... 9
9 Ductwork ................................................................... 9
9.1 Return Ductwork ......................................................9
10 Return Air Filters .................................................. 10
11 Electric Heat .......................................................... 10
12 Electrical and Control Wiring............................... 12
12.1 Building Electrical Service Inspection .................. 12
12.2 Wire Sizing..........................................................12
12.3 Maximum Overcurrent Protection (MOP) ............12
12.4 Electrical Connections – Supply Voltage .............13
12.4.1 Air Handler Only (Non-Heat Kit Models) ....13
12.4.2 Air Handler - Non-Circuit Breaker Heat Kits .....13
12.4.3 Air Handler With Circuit Breaker Heat Kit.........13
12.5 Low Voltage Connections ....................................13
12.5.1 Thermostats ....................................................13
12.6 Speed Tap Adjustment.........................................13
13 Achieving 2% Low Leakage Rate ........................ 14
14 Start-Up Procedure ............................................... 14
15 Regular Maintenance............................................ 14
16 Airflow Data .......................................................... 15
21 Wiring Diagrams................................................... 21
IO-427K
10/2014
Question and Answer IconNeed help?

Do you have a question about the Goodman ARPT60D14 and is the answer not in the manual?

Goodman ARPT60D14 Specifications

General IconGeneral
Cooling Capacity (BTU)60000
Phase1
Frequency (Hz)60
Motor TypePSC
Voltage208/230
Nominal Cooling Capacity5 Ton
Maximum External Static Pressure0.8 in. W.C.
InsulationFoil-faced

Summary

Important Safety Instructions

Pre-Installation Considerations

System Compatibility

Ensure system is AHRI approved; unmatched systems void warranty.

Installation Location and Clearances

Refrigerant Lines Installation

Flowrator Model Connections

Step-by-step guide for connecting refrigerant lines for flowrator models.

TXV Model Connections

Step-by-step guide for connecting refrigerant lines for TXV models.

Condensate Drain Lines

Ductwork Requirements

Electric Heat Installation

Electrical and Control Wiring

Wire Sizing and Voltage Drop

Guidelines for selecting appropriate wire size based on MCA and voltage drop.

Maximum Overcurrent Protection (MOP)

Requirements for NEC/CEC approved overcurrent protection devices.

Supply Voltage Electrical Connections

Low Voltage Wiring

Thermostat and Outdoor Unit Connections

Details on low voltage wiring for thermostats and outdoor units.

Speed Tap Adjustment

Start-Up Procedure Checklist

Low Voltage Wiring Diagrams

Electronic Blower Time Delay Relay

Wiring Diagrams

ARUF/ARPT Model Wiring

Specific wiring diagram for ARUF**14**/ARPT**14** models.

ASPT/ASUF Model Wiring

Specific wiring diagram for ASPT**14**/ASUF**14** models.