ProdUct SPecificationS
ProdUct SPecificationS
SS-GPC14H www.goodmanmfg.com 3
SPecificationS
Models
GPC14
24H41AC
GPC14
30H41AC
GPC14
36H41AC
GPC14
42H41AC
GPC14
48H41AC
GPC14
60H41A*
Cooling Capacity
Cooling Capacity (BTU/h) 24,000 28,400 35,600 40,000 46,000 57,500
Sensible BTU/h 18,200 21,600 27,100 30,400 35,300 40,800
SEER / EER 14.0 / 12.0 14.0 / 12.0 14.0 / 12.0 14.0 / 12.0 14.0 / 12.0 14.2 / 12.0
Decibels 76 76 78 78 80 80
AHRI Numbers 4635463 4635464 4635465 4635466 4635467 4385084
Evaporator Motor
Type EEM EEM EEM EEM EEM EEM
Wheel (D x W) 10 x 8 10 x 8 10 x 8 10 x 8 10 x 8 11 x 8
Cooling CFM 875 1,050 1,200 1,200 1,600 1,600
Fan-Only CFM 800 950 1,100 1,200 1,400 1,600
RLA 1.5 1.86 1.86 2.9 2.9 2.9
No. of Speeds 5 5 5 5 5 5
Horsepower - RPM ½ - 1050 ½ - 1050 ½ - 1050 ½ - 1050 ¾ - 1050 ¾ - 1050
Evaporator Coil
Face Area (²) 5.25 5.25 5.2 6.2 6.2 7.0
Rows Deep/ Fins per Inch 3/ 16 3/ 16 3/ 14 4/ 14 4/ 14 4/ 14
Indoor Orice Size 0.057 0.062 0.068 0.072 0.078 0.088
Filter Size (") 20 x 20 x 1 20 x 25 x 1 25 x 25 x 1 (2) 20 x 20 x 1 (2) 20 x 20 x 1 (2) 20 x 25 x 1
Drain Size (NPT) ¾" ¾" ¾" ¾" ¾" ¾"
Refrigerant Charge (oz.) 59 53 65 94 90 190
Condenser Fan / Coil
Horsepower - RPM 1/6 - 815 1/6 - 815 ¼ - 830 ¼ - 1075 ¼ - 1075 ¼ - 1075
RLA/LRA 1.1 / 1.7 1.1 / 1.7 1.5 / 3.0 1.4 / 2.9 1.4 / 2.9 1.4 / 2.9
Fan Diameter/ # Fan Blades 22 / 2 22 / 2 22 / 3 22 / 4 22 / 4 22 / 4
Face Area (²) 12.3 12.3 12.3 16 19.5 19.1
Rows Deep/ Fins per Inch 1 / 26 1 / 26 1 / 26 1 / 28 1 / 28 2 / 16
Compressor
Quanty / Type 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll
Stage Single Single Single Single Single Single
Compressor RLA/LRA 13.5 / 58.3 12.8 / 64 16.7 / 79 17.9 / 112 19.9 / 109 26.4 / 134
Electrical Data
Voltage-Phase 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1
Indoor Blower FLA 1.5 1.86 1.86 2.9 2.9 2.9
Outdoor Fan RLA 1.1 1.5 1.5 1.4 1.4 1.4
Total Unit Amps 16.1 15.76 20.06 22.2 24.2 30.7
Min. Circuit Ampacity¹ 19.5 19 24.2 26.6 29.1 37.3
Max. Overcurrent Protecon (amps)² 30 30 40 40 45 60
Ship Weight (lbs) 290 290 370 370 400 400
Operating Weight (lbs) 280 280 360 360 390 390
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.