16
APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - STANDARD
NOTES:
High static airflow requires installation of high static kit (HSKT240), or factory-built High Static model.
Unit factory shipped with sheave set at 2.5 turns open.
Air flow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2
--- --- --- --- --- --- --- --- --- --- 7203 2.18 6718 1.94
0.4
--- --- --- --- --- --- 7306 2.54 6777 2.14 6257 1.80 5711 1.66
0.6
--- --- 7477 2.97 6899 2.51 6323 2.10 5716 1.72 5103 1.39 ---
0.8
7112 2.96 6467 2.46 5795 2.01 5101 1.61 --- --- --- --- --- ---
1.0
5983 2.38 5190 1.89 --- --- --- --- --- --- --- --- --- ---
1.2 4426 1.71 --- --- --- --- --- --- --- --- --- --- --- ---
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2
--- --- --- --- --- --- --- --- --- --- --- ---
9664 4.05
0.4
--- --- --- --- --- --- --- ---
9570 4.08 9197 3.82 8702 3.51
0.6
--- --- --- --- --- ---
9038 3.82 8460 3.46 7949 3.14
--- ---
0.8
--- ---
8171 2.93 7630 3.70 7068 2.79
------------------
1.0
--- ---
7901 2.85 7203 3.42
--- --- --- --- --- --- --- ---
1.2 7344 4.35
--- --- --- --- --- --- --- --- --- --- --- ---
CPC240 STANDARD BELT DRIVE
ESP, In H
2
O
TURNS OPEN
0123456
CPC180 STANDARD BELT DRIVE
ESP, In H
2
O
TURNS OPEN
0123456