765041982 Rev. 000 22
The user menu
The user menu is opened by pressing the
button for approx. 3
seconds.
Navigate through the menu using the using the
+
and
-
buttons, after which the selected
menu item is opened with the button
P
. The
+
and
-
buttons increase or decrease the
value. They are also used to navigate around in the submenu ("LAL"). The manner of
procedure is the same in the submenu. Altered values are saved by pressing on
P
(receipt
acoustic signal!). The menu items or the menu are exited by pressing
.
Menu item Description Settings range Factory
settin
DC
Dry cooling function *
Activation: "ON"
Deactivation: "OFF"
OFF
LAL Local alarm (display)
LHL upper boundary value for
LAL
+25 … -35 °C +25 °C
LHd
Delay for LHL
1 … 120 min / in steps of 5 minutes
60 min
DA
Door alarm 0 = off / 1 = on 1
Dad
Delay for door alarm 0 … 15 min 1
BU
Acoustic alarm for LAL 0 = off / 1 = on 1
CAL Temperature offset (sensor
harmonisation)
CA Temperature offset sensor
input A (room sensor)
-5 … +5 K / steps of 0.5 K 0.0 K
CE
Temperature offset sensor
input A (room sensor)
-5 … +5 K / steps of 0.5 K 0.0 K
ALL
Relative (escorted) or
absolute (fixed) alarm limits
ESC = escorted / FAS = fixed FAS
DEF
Number of defrosting cycles for
each 24 hours
0 … 8 4