Gree GMV6 DC Inverter VRF Units Service Manual
115
2.63 "F3" Low Pressure Sensor Fault
Fault display: main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
The sensor detection circuit samples the AD value of low pressure sensor and determines the range
of AD value. When the sampled AD value exceeds the limits for 30 consecutive seconds, the fault is
generated.
Possible causes:
■ Poor contact between the low pressure sensor and the main board interface;
■ Poor contact between low pressure sensor and part where the pressure is detected;
Abnormal low pressure sensor;
Abnormal low pressure sensor detection circuit.
Troubleshooting:
Yes
No
"F3" Low Pressure Sensor
Fault
Remove the foreign
matters and plug it tightly
Yes
The detection circuit may
operate impro perly
Yes
Replace the main control
board
Whether th ere is
poor contact between low pressure
sensor and th e p art where the pressu re
is d etected?
No
Whether th e interface
terminal between the main boa rd
and the sensor g ets loose or contains
foreign matter s?
Remove the foreign
matters and plug it tightly
No
Is th e p roblem so lved
after the sensor i s repla ced?

Other manuals for Gree GMV-224WM/G-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-224WM/G-X and is the answer not in the manual?

Gree GMV-224WM/G-X Specifications

General IconGeneral
BrandGree
ModelGMV-224WM/G-X
CategoryInverter
LanguageEnglish

Related product manuals