Gree GMV6 DC Inverter VRF Units Service Manual
10
Model - GMV-2525WM/G-X GMV-2590WM/G-X GMV-2655WM/G-X GMV-2720WM/G-X
Cooling current
input
A
29.0+29.0+29.0+
36.6
29.0+29.0+36.6+
36.6
29.0+36.6+36.6+
36.6
36.6+36.6+36.6+36.6
Heating current
input
A
30.2+30.2+30.2+
35.9
30.2+30.2+35.9+
35.9
30.2+35.9+35.9+
35.9
35.9+35.9+35.9+
35.9
Rated power input kW
27.41+27.41+27.41+
27.41
27.41+27.41+27.41+
27.41
27.41+27.41+27.41
+27.41
27.41+27.41+27.41+2
7.41
Rated current A
49+49+49+
49
49+49+49+
49
49+49+49+
49
49+49+49+
49
Cooling operation
range
°C -5~52 -5~52 -5~52 -5~52
Heating operation
range
°C -30~24 -30~24 -30~24 -30~24
Refrigerant type - R410A R410A R410A R410A
Refrigerant charge kg 8.3+8.3+8.3+8.3 8.3+8.3+8.3+8.3 8.3+8.3+8.3+8.3 8.3+8.3+8.3+8.3
Maximum drive IDU
NO.
unit 80(85)* 80(90)* 80(95)* 80(100)*
Gas pipe mm Φ44.5 Φ44.5 Φ44.5 Φ44.5
Liquid pipe mm Φ22.2 Φ22.2 Φ22.2 Φ22.2
Outline dimensions
(W x D x H)
mm
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
1340×775×1690+
1340×775×1690+
1340×775×1690+
1340×775×1690
Packing dimensions
(W x D x H)
mm
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
1400×830×1855+
1400×830×1855+
1400×830×1855+
1400×830×1855
Net weight kg 350+350+350+355 350+350+355+355 350+355+355+355 355+355+355+355
Gross weight kg 365+365+365+370 365+365+370+370 365+370+370+370 370+370+370+370
Note:
*The maximum connection quantity of indoor unit in the brace should be engineering customized.
3 The Range of Production Working Temperature
Cooling
Heating
Ambient temperature
-5°C ~52°C DB
-30°C ~24°C DB
Indoor temperature
14°C ~25°C WB
15°C ~27°C DB
Indoor humidity
≤80%
When the indoor units are all VRF fresh air processor, the unit operating range is as follows:
Cooling
Ambient temperature: 16°C ~45°C
Heating
Ambient temperature: -7°C ~16°C
NOTE!
If exceeding the temperature range for working, the product may be damaged, which is not within
the warranty range.