Gree GMV6 DC Inverter VRF Units Service Manual
97
No
"CF" Multi-master Units
Fault
Make sure that o nly one master
unit exists in the networ k. Afte r
redialing, power on the redialed
module s again
The main control boa rd
may be ab normal
Yes
Replace the main control
board
Yes
Whether DIP switch is diale d
properly for the master unit (SA8)
among all the modules in
the networ k?
2.40 "CJ" System Address Code Conflict
Fault display: main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
When multiple refrigerant systems are connected through the CAN2 network of the unit's main board,
only one primary system is allowed in the network.
If two or more master units' DIP switches (SA2) are detected to be master unit's DIP switches in the
network (that is, SA2 DIP switch is "00000"), the fault of multiple master units is reported.
Possible causes:
If two or more master units' DIP switches (SA2) are detected to be master unit's DIP switches,
keep only one master unit's DIP switch (SA2) to be "00000" and other master units' DIP switches (SA2)
to be different;
Abnormal DIP switch or main board.
Troubleshooting:
Yes
"CJ" System Addre ss Code
Conflict
Keep the SA2 DIP switch to be
"000 00" for o nly one master unit, and
set that for other ma ster units to be
different. Afte r re dialing, power on the
redialed units again
The detection circuit may
operate improperly
Yes
Replace the main control
board
No
Whether two or more master units'
DIP switches (SA2) are set to the master
unit's DIP switches?

Other manuals for Gree GMV-224WM/G-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-224WM/G-X and is the answer not in the manual?

Gree GMV-224WM/G-X Specifications

General IconGeneral
BrandGree
ModelGMV-224WM/G-X
CategoryInverter
LanguageEnglish

Related product manuals