Gree GMV6 DC Inverter VRF Units Service Manual
Instruction for each stage progress at the time of debugging
—
Deubugging
Progress code Status code
Meaning
Progress
Code
Code
Code
Display
04_indoor
confirmation
db ON 04 ON
××/ The
quantity
of online
indoor
Flash
LED3 displays the quantity of online indoor
units.
db ON 04 ON OC ON
Indoor unit’s quantity inspection is finished.
Enter into the next step automatically.
05_
detect
internal
communicatio
n
db ON 05 ON C2 ON
The system has detected “communication
malfunction between main control and inverter
compressor driver”.
db ON 05 ON C3 ON
The system has detected “communication
malfunction between main control and inverter
fan driver”.
db ON 05 ON CH ON
Indoor/outdoor unit’s “rated capacity ratio is
db ON 05 ON CL ON
Indoor/outdoor unit’s “rated capacity ratio is
db ON 05 ON OC ON
System inspection is finished. Enter into the
06_
outdoor
components
confirmation
db ON 06 ON
correspod
ing error
ON
The system has detected the fault of outdoor
unit’ components.
db ON 06 ON OC ON
The system detected that there’s no outdoor
unit fault. Enter into the next step
07_indoor
unit
componets
inspection
db
ON
07
ON
XXXX/cor
error
code
ON
The system detected an indoor unit fault.
XXXX indicates engineering number of fault
indoor unit, and the corresponding fault code
is displayed 2s later. For example, if there is
D5 fault in the No. 100 indoor unit, LED3
displays as follows: 01 (after 2s) 00 (after 2s)
d5, and they will be displayed circularly.
db ON 07 ON OC ON
The system detected that there’s no outdoor
unit fault. Enter into the next step
08_compress
or reheat
comfirmation
Preheat time for compressor is insufficient.
db ON 08 ON OC ON
Preheat time for compressor is enough. Enter
into the next step automatically.
judge before
startup
db ON 09 ON U4 ON
The system refrigerant is insufficient. Please
charge the refrigerant until the fault is
db ON 09 ON OC ON
The system refrigerant judge is normal. Enter
into the next step automatically.
10_ status
judgment of
before
Starting up the operation.
Main pipeline status is abnormal.
db ON 10 ON OC ON Main pipeline status is normal.