Gree GMV6 DC Inverter VRF Units Service Manual
46
After selecting the function to be set, press the SW3 confirm button to enter the function setting. The
master module displays as follows:
LED1
LED2
LED3
Function Name
Function
code
Display
status
Current
process
Display
status
Current
status
Display
status
A7
On
00
Blinks
00
Blinks
Outdoor unit silence
A6 On 00 Blinks 00 Blinks
Cooling/heating of the entire
system
A2
On
00
Blinks
00
Blinks
Refrigerant recycle
A8
On
00
Blinks
00
Blinks
After-sales vacuum pumping
n0
On
01
Blinks
00
Blinks
Auto energy saving
n3
On
00
Blinks
00
Blinks
Forced defrosting
n4
On
00
Blinks
00
Blinks
Forced energy saving
n5 On 00 Blinks 00 Blinks
Indoor unit engineering SN
offset
qJ
On
00
Blinks
00
Blinks
One-button drainage
IG
Blinks
00
Blinks
00
Blinks
Outdoor unit static pressure
C8 On 00 Blinks 00 Blinks Compressor emergency setting
CA
On
00
Blinks
00
Blinks
Module emergency setting
C9
On
00
Blinks
00
Blinks
Fan emergency setting
1b Blinks 00 Blinks 00 Blinks
Adaptive control of weather
parameters
1C
Blinks
00
Blinks
00
Blinks
Continuous heating
1F
Blinks
00
Blinks
00
Blinks
SRL low-pressure control
1G
Blinks
00
Blinks
00
Blinks
Outdoor static pressure setting
1H
Blinks
00
Blinks
00
Blinks
Efficient module rotation
4n
Blinks
00
Blinks
00
Blinks
Adaptive control of noise
4q Blinks 00 Blinks 00 Blinks
Forced switch of the electric
heater of an indoor unit
5L
Blinks
00
Blinks
00
Blinks
Fan reverse dust removal
5n
Blinks
00
Blinks
00
Blinks
Fan anti-snow
Then, set the function/parameter accordingly.
After entering the function/parameter setting status, press the SW4 back button to return to the previous
process or exit the function setting status. If you do not press any button in 5 minutes, the system will
automatically exit the current screen and the unit will resume displaying the current status.
4.2.3.1 "A2" Refrigerant Recycle
Introduction:
This function is mainly used to recycle some refrigerant in the faulty module or the indoor unit pipeline
during unit maintenance. The table below lists the maximum amount of refrigerant that can be recycled:
Basic Module Model
Maximum Amount of Refrigerant to Be Recycled
GMV-224WM/G-X
6.0
GMV-280WM/G-X
6.0
GMV-335WM/G-X
6.0
GMV-400WM/G-X
8.5
GMV-450WM/G-X
8.5
GMV-504WM/G-X
8.5
GMV-560WM/G-X
13.0
GMV-615WM/G-X
13.0

Other manuals for Gree GMV-280WM/G-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-280WM/G-X and is the answer not in the manual?

Gree GMV-280WM/G-X Specifications

General IconGeneral
BrandGree
ModelGMV-280WM/G-X
CategoryInverter
LanguageEnglish

Related product manuals