Gree GMV6 DC Inverter VRF Units Service Manual
The master unit memorizes this setting and does not clear it even upon power failure and power-on
again. The default value is 00.
4.2.3.17 1H Efficient Module Rotation
Setting steps:
Enter the function setting. The master unit displays as follows by default, and other basic modules
display normal working status:
Press the SW1 up button and the SW2 down button to select the corresponding module rotation mode.
LED1 LED2 LED3
Description
Function
Display
Current
Display
Current
Display
1H On 00 Blinks OC Blinks Efficient module rotation
After selecting the corresponding value, press the SW3 confirm button. The master module displays
as follows:
The master unit memorizes this setting and does not clear it even upon power failure and power-on
again. The default value is 00.
4.2.3.18 4n Adaptive Control of Noise
Setting steps:
Enter the function setting. The master unit displays as follows by default, and other basic modules
display normal working status:
Press the SW1 up button and the SW2 down button to select the corresponding low pressure control
mode.
LED1 LED2 LED3
Description
Function
Display
Current
Display
Current
Display
4n On 00 Blinks OC Blinks
The adaptive control of
4n On 01 Blinks OC Blinks
The adaptive control of