Ultra Heat GMV5 User Manual
13
Fig. 13 Fig. 14
Pipe Diameter
Tightening Torque
6mm(1/4inch)
15-30N·m(11-22ft.-1b.)
9.5mm(3/8 inch)
35-40N·m(26-29ft.-1b.)
12.7mm(1/2 inch)
45-50N·m(33-37ft.-1b.)
16mm(5/8 inch)
60-65N·m(44-48ft.-1b.)
4.3.4 Outdoor Pipe Connection
Twist the flared nut on the connection pipe of outdoor valves. Twisting method is the same as
for indoor pipe connection.
According to customer requirement or space limit, outlet pipe can be installed from the front,
right or rear side.
Fig. 15
4.3.5 Installation of Y-type Branch
(1) Y-type Branch