Precondition: No refrigerant exists in the pipeline system and the power supply has been disconnected.   
3. Disassemble the oil 
separator.   
●
Use a screwdriver to unscrew 
the oil separator. 
 
●
Loosen the electric heating belt.   
●Heat the four pipe joints of the 
oil separator by welding and 
remove the connecting pipes.   
Note: Avoid nearby parts from 
being burnt during welding.   
4. Remove the oil 
separator.   
●Remove the oil separator from 
the chassis.   
5. Install a new oil 
separator.   
●Weld the four pipe joints with 
the oil separator.   
During welding, charge nitrogen 
into the pipes. The pressure 
should be controlled within 
0.5±0.1 kgf/cm2 (relative 
pressure). 
Note: Avoid nearby parts from 
being burnt during welding.   
●Screw the oil separator.   
●