GREE                                                                        GMV5E DC INVERTER VRF UNITS SERVICE MANUAL 
    89   
 
⑦ n4 Highest capacity output limitation settings 
Step  1:  Confirm  entering  the  n4  highest  capacity  output  limitation  settings.  The  master  unit  is 
displayed as follows: 
Step 2: Select a corresponding capacity limitation value by pressing "SW1 (UP)" or "SW2 (DOWN)". 
Step 3: Press "SW7" to confirm selecting the mode. The master module is displayed as follows: 
If  no  button  operations  are  performed  on  the  master  unit  for  five  minutes,  the  function  setting 
automatically quits and the unit restores the current status. (Press "SW6" in setting status to return to the 
upper level; press "SW6" after settings are completed to restore the normal operating status of the unit.) 
⑧ n5 Indoor unit project number offset settings 
Step 1: Confirm entering the n5 IDU project number offset settings. The master unit is displayed as 
follows: 
Step 2: Press "SW7" to send the project number offset command. The master module is displayed 
as follows: 
After 10 seconds, the system quits this mode and restores the normal operation mode. 
Note:  This  function  only  needs  to  be  set  on  the  master  system,  which  is  the  system  with  the 
centralized control address SA2  DIP switch  being  "00000".  For details, see the "Centralized  Control 
Address DIP Switch (SA2_Addr-CC)" section. 
2.2.4 Function Query Operations 
Step 1: Open the commissioning window of the master unit panel. 
Step 2: Power on the entire unit. 
Step 3: Press "SW4" on the master unit to enter the query status.   
Step 4: Select a function to be queried by pressing "SW1 (UP)" or "SW2 (DOWN)" on the master