GREE                                                                        GMV5E DC INVERTER VRF UNITS SERVICE MANUAL 
    90   
unit. By default, the A7 outdoor silent mode is displayed for query. 
For example, select the A6 unit cooling/heating function. The display is as follows: 
Step 5: If the n8 IDU address query is selected, the display is as follows. Enter the to-be-confirmed 
status of IDU project number query. 
Press  "SW7"  and  select  the  IDU  project  number  query  on  the  master  unit.  The  master  unit  is 
displayed as follows. Other modules are displayed in normal status. 
Regardless of the current display status of wired controllers or display panels of all IDUs, the current 
display status is all switched to the IDU project number. However, it does not influence the settings and 
operation status of outdoor and IDUs.   
On the master unit, press "SW6" to return to the upper level. The IDU retains the project number 
display status.   
On the master unit, press and hold "SW6" to quit the address display status for all IDUs and return 
to the upper level. 
If no quit button operations are performed on the master unit for 30 minutes, the function setting 
automatically quits and the unit restores the current status.   
Step 6: If the n9 IDU address query is selected, the display is as follows: 
Number of IDUs (Thousands-place 
Hundreds-place) 
Number of IDUs (Tens-place 
Ones-place) 
The digital LED2 displays the number of IDUs (thousands-place hundreds-place) and the digital 
LED3 displays the number of IDUs (tens-place ones place). For example, if the number of IDUs is 75, 
"0075" is displayed.   
If  no  button  operations  are  performed  on  the  master  unit  for  five  minutes,  the  function  setting 
automatically quits and the unit restores the current status.   
Note: 
The online IDU quantity query function applies to a single refrigerating system only. 
Step 7: If the n6 fault query is selected, the display is as follows. Enter the to-be-confirmed status of 
fault query. 
Press "SW7" on the master unit to confirm fault query.   
Select a fault to be queried by pressing "SW1 (UP)" or "SW2 (DOWN)". LED3 alternately displays