GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 
210 
Precondition: No refrigerant exists in the pipeline system and the power supply has been disconnected.   
1. Loosen the hooks 
at the bottom of the 
electric box and the 
screws.   
●
Remove the upper and lower 
front panels. 
 
●
Loosen the hooks at the 
bottom of the electric box. 
 
●
Use a screwdriver to unscrew 
the electric box. 
 
2. Remove the 
electric box.   
●Disconnect internal and 
external connecting lines of the 
electric box.   
●Protect the internal parts 
during the disassembly.   
3. Disassemble the 
electric expansion 
valve.   
●Remove the coil from the 
electric expansion valve.   
●Heat the connecting pipes of 
the electric expansion valve by 
welding and remove the pipes.   
Note: Avoid nearby parts from 
being burnt during welding.   
4. Remove the 
electric expansion 
valve.   
●Remove the electric expansion 
valve.