Gree                GMV6 DC Inverter VRF Units Service Manual 
 
After selecting the function to be set, press the SW3 confirm button to enter the function setting. The 
master module displays as follows: 
Function Name 
Function 
Display 
Current 
Display 
Current 
Display 
A6  On  00  Blinks  00  Blinks 
Cooling/heating of the entire 
After-sales vacuum pumping 
n5  On  00  Blinks  00  Blinks 
Indoor unit engineering SN 
Outdoor unit static pressure 
C8  On  00  Blinks  00  Blinks  Compressor emergency setting 
1b  Blinks  00  Blinks  00  Blinks 
Adaptive control of weather 
Outdoor static pressure setting 
Efficient module rotation 
Adaptive control of noise 
4q  Blinks  00  Blinks  00  Blinks 
Forced switch of the electric 
Then, set the function/parameter accordingly. 
After entering the function/parameter setting status, press the SW4 back button to return to the previous 
process or exit the function setting status. If you do not press any button in 5 minutes, the system will 
automatically exit the current screen and the unit will resume displaying the current status. 
4.2.3.1 "A2" Refrigerant Recycle 
Introduction: 
This function is mainly used to recycle some refrigerant in the faulty module or the indoor unit pipeline 
during unit maintenance. The table below lists the maximum amount of refrigerant that can be recycled: 
Maximum Amount of Refrigerant to Be Recycled