Gree                GMV6 DC Inverter VRF Units Service Manual 
 
Yes
No
No
"b5" Subcooler's  G as 
Outlet Temperature  Sensor 
Fault
Whether  th e interface 
terminal between the  main boa rd and 
temperature sensor gets loose or 
contains forei gn matters?
Remove the  foreign 
matters and plug  it tightly
Whether  th e temperatur e 
sensor is abn ormal?
Yes
Replace  the tempera ture 
sensor
The  detection  circuit may 
operate  impro perly
Yes
Replace  the main control 
board
 
 
2.22 "b6" Suction Temperature Sensor 1 Fault 
Fault display: main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit 
display   
Fault diagnosis: 
The temperature sensor detection circuit samples the AD value of temperature sensor and 
determines the range of AD value. When the sampled AD value exceeds the limits for 30 consecutive 
seconds, the fault is generated. 
Possible causes: 
■ Poor contact between the temperature sensor and the main board interface; 
■ Abnormal temperature sensor; 
■ Abnormal detection circuit. 
Troubleshooting: