Gree                GMV6 DC Inverter VRF Units Service Manual 
 
2.69 "FA" Discharge Temperature Sensor Fault of Compressor 6 
Fault display: main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit 
display   
Fault diagnosis: 
The temperature sensor detection circuit samples the AD value of temperature sensor and 
determines the range of AD value. When the sampled AD value exceeds the limits for 30 consecutive 
seconds, the fault is generated. 
Possible causes: 
■ Poor contact between the discharge temperature sensor and the main board interface; 
■ Abnormal discharge temperature sensor; 
■ Abnormal detection circuit. 
Troubleshooting: 
Yes
"FA" Discharge 
Temperature Sen sor Fault 
of Compressor 6
Remove the  foreign 
matters and plug  it tightly
The  detection  circuit may 
operate  impro perly
Yes
Replace  the main control 
board
No
Whether  th e interface 
terminal between the main board 
and the temperature sensor gets loose or 
contains forei gn matters?
No
Replace  the tempera ture sensor