Gree                GMV6 DC Inverter VRF Units Service Manual 
 
2.70 "FH" Abnormal Current Sensor of Compressor 1 
Fault display: main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit 
display   
Fault diagnosis: 
The circuit detection circuit samples the AD value and determines the range of AD value. When the 
sampled AD value exceeds the limits for 3 consecutive seconds, the fault is generated. 
Possible causes: 
■ Poor contact between the circuit sensor and the main board interface; 
■ Abnormal small board of circuit sensor; 
■ Abnormal detection circuit.
 
Troubleshooting: 
Yes
"FH" Abnormal Cur rent 
Sensor  of  Compressor  1
Remove the  foreign 
matters and plug  it tightly
The  detection  circuit may 
operate  impro perly
Yes
Replace  the main control 
board
No
Whether  th e interface 
terminal between the main board 
and the temperature sensor gets loose or 
contains forei gn matters?
No
Is th e p roblem  solve d after the small 
board o f circu it se nsor is replaced?