2.71 "FC" Abnormal Current Sensor of Compressor 2 
Fault display: main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit 
display   
Fault diagnosis: 
The circuit detection circuit samples the AD value and determines the range of AD value. When the 
sampled AD value exceeds the limits for 3 consecutive seconds, the fault is generated. 
Possible causes: 
■ Poor contact between the circuit sensor and the main board interface; 
■ Abnormal small board of circuit sensor; 
■ Abnormal detection circuit. 
Troubleshooting:
 
Yes
"FC" Abnormal Cur rent 
Sensor  of Compressor 2
Remove the foreign 
matters and  plug it tightly
The  detection  circuit may 
operate  improperly
Yes
Replace  the main control 
board
No
Whether th e i nter face 
terminal between the  main boa rd 
and the te mpe rature sensor gets loose or 
contains forei gn matters?
No
Is th e p roblem so lved after  the  small 
board o f circu it se nsor is replaced?