EasyManua.ls Logo

Gree GMV BACnet

Gree GMV BACnet
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GMV BACnet Gateway Technical Service Manual
4
2.2.4 INTERFACE
1Diagram of interface
CAN communication
interface connected
to the AC unit
Power input
Communication interface
of ethernet, used for
remote control
monitoring communication
Reserve 5-way
input IO port
Reserve 5-way
output IO port
2Power
The input power is 100VAC-240VAC,50/60Hz.
WARNING! The ground protection of power input port must be connected; otherwise it
might be dangerous; besides, when the gateway is energized, don’t touch the power input.
Note: the power cord shall be fixed with bonding clamp in the kit, as shown in the fig.
3Communication interface
CAB communication interface: connect it to the AC unit through the 2-core communication
line to realize the communication between BACnet gateway and the AC which adopts CAN
protocol.
RS485-1 communication interface: this device will not use this communication interface
temporarily.
RS485-2 communication interface: this device will not use this communication interface
temporarily.
USB and SD card interface:
this device will not use this interface temporarily.
Ethernet interface:
realize communication through network cable and BMS.

Related product manuals