GMV BACnet Gateway Technical Service Manual
6
the routing shown is for reference only.
3.2 COMMUNICATION CONNECTION
BACnet gateway communication system includes
1The communication between BACnet gateway and BMS;
2The communication between BACnet gateway and AC units.
3.2.1 MATERIAL SELECTION FOR COMMUNICATION LINE
1Model selection of BACnet gateway and BMS communication line shall use standard
Ethernet communication line, the length of network cable between gateway and router (computer,
switchboard, etc.) shall not exceed 80m;
2Communication line model selection for BACnet gateway and AC unit
Wire type
Communication
line between
gateway and
AC units(m)
Wire diameter(mm
2
)
Wire standard
Remark
Light-weight/normal
PVC jacket twisted
copper wire(RVV)
L
500
2
0.75
GB/T
5023.5-2008
Total communication
length shall not exceed
500m
3.2.2 COMMUNICATION CONNECTION METHOD
1Communication connection between BACnet gateway and BMS.
2Communication connection between BACnet gateway and AC units (n is the quantity of
ODU system, n ≤ 16);
Notice! All communication connection lines under BACnet gateway must be in series
connection, star connection shall not be adopted.