EasyManua.ls Logo

Gree GMV-ND22PLS/A-T

Gree GMV-ND22PLS/A-T
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Multi Variable Air Conditioners Duct Type Indoor Uni
15
4.4 Installation of Air Duct
Notes:
There should be insulating layer on air-out duct, air-return duct and fresh air duct to avoid
heat loss and moisture. Adhere a nail on the air duct and then add thermal sponge with a layer of
tin. Fasten it with a nail cover and then seal the junction with tin tapes; You can also use other
materials that have good insulation quality.
Each air-out duct and air-return duct should be fixed on a pre-made board with iron frame.
The junction of air duct should be well-sealed in order to prevent air leakage.
The design and construction of air duct should comply with national requirements.
The edge of air-return duct is suggested to be more than 150mm away from the wall. Add
a filter to the air-return opening.
Please consider noise-damping and vibration damping for the design and construction of
air duct. Besides, noise source must be away from people. For instance, do not have the
air-return opening installed on top of the user(offices, rest area, etc.).
4.4.1 Installation of Air-out Duct
(1) Installation of the Rectangular Duct
Fig 4.4.1
No.
Name
No.
Name
1
Hanger Rod
5
Static Pressure Box
2
Return Air Duct
6
Filter Screen
3
Canvas Duct
7
Main Supply Air Duct
4
Return Air Inlet
8
Supply Air Outlet
(2) Installation of Circular Duct
Fig 4.4.2

Other manuals for Gree GMV-ND22PLS/A-T

Related product manuals