Selection of Installation Location and Precautions
If choose the indoor unit with auxiliary electric heater which decides the capacity of circuit breaker. Below is
the circuit breaker models which should be specially configured.
Model of Indoor Units(with
auxiliary electric)
Capacity of Circuit Breaker
Min. Sectional Area of
Earth lead (mm
2
)
Min. Sectional Area of
Power Cord (mm
2
)
22283236 duct type units
10 1.0 1.0
404550duct type units
13 1.5 1.5
56637180duct type units
20 2.5 2.5
90100112125140 duct
type units
13 1.5 1.5
28364550 cassette type
units
10 1.0 1.0
566371 cassette type units
13 1.5 1.5
8090112125 cassette type
units
13 1.5 1.5
2225283236 ultra-thin
duct units
10 1.0 1.0
404550 ultra-thin duct units
13 1.5 1.5
566371 ultra-thin duct units
16 2.5 2.5
Noise Control
Install the unit at a well-ventilated place; otherwise it might result in decreased working capacity or higher
noise.
Install the unit securely on a base that can fully support its weight; otherwise vibration and noise might be
caused.
Install the outdoor unit so that the hot air or noise will not disturb your neighb ors.
Do not place any obstacle close the outlet of outdoor unit; otherwise it might result in decreased working
capacity or higher noise.
If the air conditioner gives out abnormal noise during use, please immediately contact your dealer.