28
Connection of Indoor and Outdoor Unit
The diameter of the piping from the end branch pipe of outdoor unit to the first branch pipe of indoor unit
shall be selected according to the capacity of combined basic modules as below:
Piping Connections
Multple Model Uses combination of
Lquid
pipe
(mm)
Low-pressure
gas pipe
(mm)
High-pressure
gas pipe
(mm)
GMV-Pdhm504W2/Na-M
GMV-Pdhm224W/Na-M
;
GMV-Pdhm280W/Na-M Φ15.9 Φ28.6 Φ22.2
GMV-Pdhm560W2/Na-M
GMV-Pdhm280W/Na-M
;
GMV-Pdhm280W/Na-M Φ15.9 Φ28.6 Φ28.6
GMV-Pdhm615W2/Na-M
GMV-Pdhm280W/Na-M
;
GMV-Pdhm335W/Na-M Φ15.9 Φ28.6 Φ28.6
GMV-Pdhm680W2/Na-M
GMV-Pdhm280W/Na-M
;
GMV-Pdhm400W/Na-M Φ15.9 Φ34.9 Φ28.6
GMV-Pdhm730W2/Na-M
GMV-Pdhm280W/Na-M
;
GMV-Pdhm450W/Na-M Φ19.1 Φ34.9 Φ28.6
GMV-Pdhm800W2/Na-M
GMV-Pdhm400W/Na-M
;
GMV-Pdhm400W/Na-M
Φ19.1 Φ34.9 Φ28.6
GMV-Pdhm850W2/Na-M
GMV-Pdhm400W/Na-M
;
GMV-Pdhm450W/Na-M Φ19.1 Φ34.9 Φ28.6
GMV-Pdhm900W2/Na-M
GMV-Pdhm450W/Na-M
;
GMV-Pdhm450W/Na-M Φ19.1 Φ34.9 Φ28.6
GMV-Pdhm960W3/Na-M
GMV-Pdhm280W/Na-M
;
GMV-Pdhm280W/Na-M
;
GMV-Pdhm400W/Na-M Φ19.1 Φ34.9 Φ28.6
GMV-Pdhm1010W3/Na-M
GMV-Pdhm280W/Na-M
;
GMV-Pdhm280W/Na-M
;
GMV-Pdhm450W/Na-M
Φ19.1 Φ41.3 Φ28.6
GMV-Pdhm1070W3/Na-M
GMV-Pdhm280W/Na-M
;
GMV-Pdhm335W/Na-M
;
GMV-Pdhm450W/Na-M
Φ19.1 Φ41.3 Φ34.9