36
Connection of Indoor and Outdoor Unit
Outdoor unit is higher than indoor unit
e. Fabrication dimension of oil trap is as shown below:
A B(mm) C(mm)
mm inch
Φ19.0
3/4
34 150
Φ22.2
7/8
31 150
Φ25.4
1/1
45 150
Φ28.6 9/8
45 150
Φ34.9 11/8
60 250
Φ38.1 12/8
60 350
Φ41.3 13/8
80 450
Φ44.45 7/4
90 500
Φ54.1 17/8
90 500
Oil trap
Oil trap
Oil trap