53
Communication of the System
1. Address setting of indoor untis
Cautions as setting address of indoor units
1. Indoor units connected with a same pinboard whose address can be set as 1~16 # but addresses cannot
be reduplicative.
2. Addresses of indoor units connected with different pinboard can be the same.
Mainboard of
outdoor units
Module Qty
code SW2
Address code SA1
of pinboard
Module address code SW3