Multi Variable Air Conditioners Duct Type Indoor Unit
7
3.4 Wiring Requirements
(1) Power Cord Size and Air Switch Capacity.
Model Power Supply
Air Switch
Capacity(A)
Minimum Sectional
Area of Ground
Wire(mm
2
)
Minimum Sectional
Area of Power
Cord(mm
2
)
GMV-ND22PL/B-T
220~240V-1Ph-50Hz
208~230V-1Ph-60Hz
6 1.0 1.0
GMV-ND25PL/B-T 6 1.0 1.0
GMV-ND28PL/B-T 6 1.0 1.0
GMV-ND32PL/B-T 6 1.0 1.0
GMV-ND36PL/B-T 6 1.0 1.0
GMV-ND40PL/B-T 6 1.0 1.0
GMV-ND45PL/B-T 6 1.0 1.0
GMV-ND50PL/B-T 6 1.0 1.0
GMV-ND56PL/B-T 6 1.0 1.0
GMV-ND63PL/B-T 6 1.0 1.0
GMV-ND72PL/B-T 6 1.0 1.0
GMV-ND22PLS/B1-T 6 1.0 1.0
GMV-ND25PLS/B1-T 6 1.0 1.0
GMV-ND28PLS/B1-T 6 1.0 1.0
GMV-ND32PLS/B1-T 6 1.0 1.0
GMV-ND36PLS/B1-T 6 1.0 1.0
GMV-ND40PLS/B1-T 6 1.0 1.0
GMV-ND45PLS/B1-T 6 1.0 1.0
GMV-ND50PLS/B1-T 6 1.0 1.0
GMV-ND56PLS/B1-T 6 1.0 1.0
GMV-ND63PLS/B1-T 6 1.0 1.0
GMV-ND71PLS/B1-T 6 1.0 1.0
GMV-ND18PLS/C-T 6 1.0 1.0
GMV-ND22PLS/C-T 6 1.0 1.0
GMV-ND25PLS/C-T 6 1.0 1.0
GMV-ND28PLS/C-T 6 1.0 1.0
GMV-ND32PLS/C-T 6 1.0 1.0
GMV-ND36PLS/C-T 6 1.0 1.0
GMV-ND40PLS/C-T 6 1.0 1.0
GMV-ND45PLS/C-T 6 1.0 1.0
GMV-ND50PLS/C-T 6 1.0 1.0
GMV-ND56PLS/C-T 6 1.0 1.0
GMV-ND63PLS/C-T 6 1.0 1.0
GMV-ND71PLS/C-T 6 1.0 1.0
NOTICE:
Use copper wire only as unit's power cord. Operating temperature should be within its rated