EasyManua.ls Logo

Gree GRS-CQ16Pd/NhG-M - Selection of the AC Contactor

Gree GRS-CQ16Pd/NhG-M
180 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Air-to-water Heat Pump
51
MONOBLOC
TYPE
(4) Selection of the AC Contactor
The AC contactors have not equipped for the unit before delivery. Therefore, the AC contactors for the auxiliary
electric heater 1, auxiliary electric heater 2 and water tank heater should be installed on site. See the table below
for reference technical data.
Name
Rated
Frequency
Rated coil voltage
Rated working voltage for
the main circuit
Rated working current for the
main circuit
AC contactor 50Hz 220V 220V 25A
See gures below for more wiring instructions:
GRS-CQ4.0Pd/NhG-K, GRS-CQ6.0Pd/NhG-K,GRS-CQ8.0Pd/NhG-K,GRS-CQ10Pd/NhG-K, GRS-CQ12Pd/
NhG-K, GRS-CQ14Pd/NhG-K, GRS-CQ16Pd/NhG-K
GRS-CQ10Pd/NhG-M, GRS-CQ12Pd/NhG-M, GRS-CQ14Pd/NhG-M, GRS-CQ16Pd/NhG-M
Case 1
KM1
A2
12 13 14
380-415V,3N~ 50HZ
380-415V,3N~ 50HZ
380-415V,3N~ 50HZ
A11
L1 L3L2
3
5
6
2
2
2
4
6
KM 2
A2
15 16 17
A1 1
L1 L3L2
35
4
6
KM 3
A2
18 19 20
A1 1
L1 L3L2
35
4
XT3
XT3
XT3
Optional E-heater 1 Optional E-heater 2 Water Tank E-heater
Case 2
380-415V,3N~ 50HZ
380-415V,3N~ 50HZ
380-415V,3N~ 50HZ
KM1
A2
12 13 14
A1
5
L1 L3L2
3
3
1
1
3
1
2
2
6
6
4
5
KM 2
15 16 17
A1
L1 L3L2
4
5
KM3
18 19
A1
L1 L3L2
2
6
4
A2
A2
Optional E-heater 1 Optional E-heater 2 Water Tank E-heater