INSTALLATION 
1 INDOOR UNIT INSTALLATION 
1.1 Installation of Duct Type 
1.1.1 Before Installation 
After  receiving  the  machine,  please  check  for  any  transport  damage.  If  finding  any  surface  or 
internal damage, please immediately report to the transport company or equipment company in writing. 
After receiving the machine, please check the unit and accessories in reference to the packing list. 
Ensure  that  the  model  is  correct  and  the  machine  is  in  good  condition.  Please  also  check  if  the 
specification and quantity of accessory parts are correct. 
Determine the correct handling route and methods, thus to avoid damaging the unit or causing 
possible  hazard.  For  the  sake  of  protection  and  safety,  it  is  suggested  to  move  the  unit  with  the 
packaging box. Even though it is not permitted to do like this under special occasions, do not remove the 
packaging box, thus to avoid loosening or falling during handling.   
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of 
the building, make sure that the electrical insulation must comply with applicable standards.   
Ensure  that  the  place  of  installation  is  far  from  the  area  where  the  inflammable  or  explosive 
substances are stored, thus to avoid possible explosion or fire due to leakage.   
1.1.2 Installation Site 
Ensure the top hanging piece has strong strength to withstand the weight of the unit. 
The drainage pipe has convenient flow of water. 
There is no  obstacle blocking the return air inlet and exhaust outlet, so  as to ensure sound air 
circulation. 
The installation spaces required by the drawing must be ensured, so as to provide enough space for 
the service and maintenance. 
The installation site must be far away from heat source, leakage of inflammable gas or smoke. 
The indoor unit is of ceiling mount (indoor unit is hidden inside the ceiling). 
The indoor and outdoor units, the power cable and the connecting electrical lines must be at least 1 
meter from any TV set or radio. This is to avoid image interference or noise of the TV set or radio. (Even 
if the distance is 1 meter, noise can also exist if there is strong electric wave.) 
1.1.3 Caution for Installation 
Generally, the unit is installed indoor on ceiling. For ceiling mounting, ensure that the hangers on 
ceiling have adequate strength to support the weight of the unit. 
To  meet  the  noise  and  vibration  requirements,  the  unit  shall  be  installed  by  using  rubber  pad 
(thickness≥20mm) and rubber connector. 
Insert a M10 expansion bolt into the hole. Drive a nail into the bolt. Refer to the profile dimensions 
drawing of the indoor unit for the distance between the holes. Refer to Figure 3-1-1 for the installation of 
the expansion bolt.